EOCRFEZWRAF7WAQ
The Schneider Electric EOCRFEZWRAF7WAQ is an electronic overload relay from the EOCR-FEZ series. It is designed for comprehensive motor protection in industrial applications, providing advanced protection features for three-phase AC motors with digital monitoring, communication capabilities, and wide adjustment ranges.
DESCRIBE
Electrical Data
Product Type: Electronic overload relay with digital display
Rated Insulation Voltage: 690 V AC maximum
Rated Operational Voltage: Up to 690 V AC (three-phase)
Frequency: 50/60 Hz
Control Supply Voltage: 100...240 V AC/DC (typical for "A" variant)
Power Consumption: < 10 VA
Current Settings
Current Range: Adjustable wide range 10-120 A (typical for "W" variant)
Overload Setting: Adjustable via keypad with digital display
Trip Class: Selectable (typically Class 5, 10, 15, 20, 30, 40)
Phase Loss Sensitivity: Trip within 3 seconds (typical)
Phase Imbalance Protection: Adjustable (typically 5-50%)
Ground Fault Protection: Adjustable (typically 0.03-10 A)
Protection Functions
Overload Protection: Thermal model with selectable trip curves
Phase Loss Protection: Instantaneous trip upon phase failure
Phase Reversal Protection: Detects incorrect phase sequence
Phase Imbalance Protection: Adjustable trip level
Ground Fault Protection: Residual current detection
Undercurrent Protection: For load loss detection (pumps, conveyors)
Jam Protection: For sudden overload conditions
Stall Protection: For locked rotor conditions
Short Circuit Protection: Instantaneous trip
Current History: Records fault current values for diagnostics
Pre-Alarm: Adjustable warning before trip
Display & Interface
Display Type: Large digital LED or LCD display
Display Indications: Current per phase (A), voltage (optional), fault type, trip status, settings, historical data
Setting Method: Keypad with menu navigation
Trip Indication: Specific fault type displayed with code
LED Indicators: Power (green), trip (red), alarm (yellow), communication (green flashing)
Inputs/Outputs
Trip Relay: 2 SPDT relays (250 V AC, 5 A typical)
Alarm Relay: 1 SPDT (for pre-alarm indication)
Digital Inputs: 2 configurable (remote reset, external fault)
Analog Output: 4-20 mA (isolated, for remote current monitoring)
Communication: Modbus RTU (RS-485) with selectable baud rate
Reset Modes
Manual Reset: Via push button (local)
Auto Reset: Selectable via setting (with adjustable delay 0.5-60 seconds)
Remote Reset: Via digital input or communication
Mechanical
Mounting Mode: Direct mounting with contactor or DIN rail mount (35 mm)
Compatible Contactors: Specific TeSys D, TeSys F, or similar series contactors
Terminal Type: Screw terminals or spring terminals (depending on variant)
Wire Size (Control): 0.5...4 mm² (AWG 20-12)
Wire Size (Power): Up to 35 mm² (AWG 2) depending on current rating
Tightening Torque: According to terminal specifications
Dimensions (W x H x D): Approximately 80 mm x 110 mm x 130 mm (typical)
Net Weight: Approximately 0.8 kg
Environmental
Degree of Protection (IP): IP20 (enclosure) / IP40 (front panel)
Operating Temperature: -25...70 °C
Storage Temperature: -40...85 °C
Relative Humidity: 5...95% (non-condensing)
Vibration Resistance: 1 g (10-150 Hz)
Shock Resistance: 15 g (11 ms)
Altitude: Up to 3000 m with derating
Pollution Degree: 3 (industrial environment)
Certifications
Standards: IEC 60947-4-1, IEC 60947-5-1, UL 508, CSA C22.2 No. 14
Certifications: CE, UL, cUL, CCC, EAC
Marine Certifications: ABS, BV, DNV-GL, LR (depending on variant)
RoHS Compliance: Yes
REACH Compliance: Yes