ISEMM-WRUH
The iSEMM-WRUH is an advanced multifunctional electronic motor protection relay from the EOCR-iSEMM series, part of Schneider Electric's comprehensive motor protection portfolio (originally developed by nVent/Samwha EOCR).
DESCRIBE
Key Specifications
Parameter Value
Brand Schneider Electric / nVent (formerly Samwha EOCR)
Series EOCR-iSEMM (intelligent Smart Energy Motor Management)
Product Type Multifunctional Electronic Motor Protection Relay with Energy Management
Model / Reference iSEMM-WRUH
CT Type Window (Through-hole) type for easy installation without disconnecting power leads
Current Measurement Integrated window-type CTs
Current Setting Range • Direct measurement: 0.5-60A (with integrated CTs)
• With external CTs: Up to 960A (using CT with 5A secondary)
Voltage Measurement Direct connection up to 690V AC (phase-to-phase)
Control Voltage U: 100-240VAC/DC (wide range)
Frequency 50/60 Hz (power circuit)
Suitable for variable frequency drive applications (20-400Hz)
Protection Functions • Overcurrent (Overload)
• Undercurrent (Underload)
• Phase Loss / Open Phase
• Phase Reversal (Reverse Phase)
• Phase Unbalance / Imbalance
• Locked Rotor (Stall) at Start and Run
• Earth Fault (Ground Fault)
• Jamming
• Mechanical jam
• Short circuit protection
• Overvoltage / Undervoltage
• Underpower / Overpower
• Reverse power
• Thermal overload
Energy Management Functions • Real-time power measurement (kW, kVAR, kVA)
• Energy metering (kWh, kVARh, kVAh)
• Power factor monitoring
• Demand monitoring (current, power)
• Maximum demand recording
• Load profiling
• Efficiency monitoring
• CO₂ emissions calculation
Measurement Accuracy • Current: ±1%
• Voltage: ±0.5%
• Power: ±1%
• Energy: Class 1 (IEC 62053-21)
Time Delay Settings • Start Delay (D-TIME): 0-200 seconds
• Trip Delay (O-TIME): 0.2-120 seconds (definite) or 1-30 Class (inverse/thermal)
• Undercurrent Trip Delay (U-TIME): 0.5-120 seconds
• Earth Fault Trip Delay (E-TIME): 0.1-10 seconds
• Voltage Trip Delay (V-TIME): 0.1-30 seconds
Output Contact Configuration R-type: "Non-Fail-Safe" operation (contacts do not change state when relay is powered on/energized)
Output Contacts Multiple independent relay outputs (typically 4) for trip, alarm, and control functions
Contact Rating: 5A / 250VAC resistive
Reset Mode Manual (Instant) / Electric (Remote) / Auto selectable
Communication • Modbus RTU protocol, RS-485 interface (standard)
• Optional: Profibus-DP, DeviceNet, Ethernet/IP
Display / Indication • Large graphic LCD display for comprehensive data visualization
• Real-time current, voltage, power, energy readings
• Fault cause indication with detailed information
• LED indicators for operational status
• Trend graphs for motor parameters
• Energy consumption graphs
Monitoring Functions • Real-time 3-phase current display
• Voltage monitoring (phase-to-phase, phase-to-neutral)
• Power monitoring (active, reactive, apparent)
• Energy metering (kWh, kVARh, kVAh)
• Power factor monitoring
• Frequency monitoring
• THD (Total Harmonic Distortion) monitoring
• Fault recording with cause storage (last 10 faults)
• Operating time accumulation
• Number of starts counter
• Motor thermal capacity monitoring
• Self-diagnosis function
• Event logging (last 50 events)
• Data logging with time stamp
Mounting 35mm DIN Rail / Panel mount
Special Features • High accuracy measurement (±1% current, ±0.5% voltage)
• Records last 10 faults with detailed information (cause, values, time, date)
• Records last 50 events
• Separate display unit option available (up to 150m distance)
• PC parameter setting capability via dedicated software
• Restart limit function (0-10 times)
• Date and time setting with real-time clock
• Phase/Neutral load protection selectable
• 4-20mA analog output (multiple channels)
• Programmable logic functions
• Custom protection curves
• Energy management functions
• Predictive maintenance alerts
• Load shedding capability
• Peak demand control
• Time-of-use energy recording
Standards IEC 60947-4-1, IEC 60947-4-2, IEC 62053-21 (Energy), UL, CSA, CCC
Rated Operational Voltage (Ue) Up to 690V AC (direct voltage measurement)
Rated Insulation Voltage (Ui) 600V AC (UL/CSA) / 690V AC (IEC)
Rated Impulse Withstand Voltage (Uimp) 6 kV
Degree of Protection IP20 (relay body) / Front panel sealed (IP40)
Operating Temperature -20°C to 60°C
Storage Temperature -30°C to 80°C
Power Consumption <5W
Dimensions (W x H x D) Enhanced design for DIN rail mounting (approx. 70 x 110 x 120 mm)
Weight Approximately 0.5 - 0.6 kg
Terminal Wiring Screw clamp terminals for solid/stranded wires (1-2.5 mm² control, up to 4 mm² power/voltage)