EOCR-PMZWRDUH
The Schneider Electric EOCR-PMZ-WRDUH is a high-performance, multifunctional intelligent motor protection relay from the EOCR-PMZ series. It is based on a Microcontroller Unit (MCU) for real-time, high-precision monitoring and protection of three-phase AC motors
DESCRIBE
Parameter Value
Product Range EOCR (Electronic OverCurrent Relay) - PMZ Series
Product Type Multifunctional Intelligent Motor Protection Relay
Product Code / Model EOCR-PMZ-WRDUH (also written as EOCRPMZ-WRDUH)
Current Setting Range 0.5 ~ 100 A (definite time, direct through-hole)
0.5 ~ 60 A (inverse time/thermal inverse, direct)
Above ranges require external CTs (up to 6000A)
Ground Current Setting Range 0.03 ~ 10 A (adjustable)
Short Circuit Setting Range 2 ~ 50 × OC (up to 500A)
Control Supply Voltage (Us) 100-240 V AC/DC (85%~110% of rated voltage)
Supply Frequency 50 / 60 Hz
Power Consumption < 7 VA
Measurement Accuracy ±1% (True RMS measurement)
Protection Functions Overcurrent (OC), Undercurrent (UC), Phase Loss (Open Phase), Reverse Phase (Reversal), Locked Rotor (Stall), Current Unbalance, Ground Fault (Leakage), Short Circuit, Pre-alarm
Time Characteristics Definite Time / Inverse Time (1-30 classes) / Thermal Overload Inverse Time
Time Settings Overcurrent Trip Delay: Definite time: 0.2-30 seconds; Inverse time: 1-30 classes
Undercurrent Delay: OFF, 0.2-30 seconds adjustable
Phase Loss Trip Time: Within 3 seconds
Reverse Phase Trip Time: Within 0.1-0.3 seconds
Locked Rotor Delay: 0.1-10 seconds adjustable
Current Unbalance Trip Time: Within 8 seconds
Ground Fault Delay: 0.05, 0.1-10 seconds adjustable
Short Circuit Delay: 0-20 seconds adjustable
Display 7-segment LED (3-phase current values, ground leakage current, trip causes, setting parameters) cycles at 5-second intervals; Bar graph (load factor 65%~100%)
Communication Modbus RTU / RS-485 (up to 200 nodes)
Analog Outputs Dual 4-20 mA (isolated)
Output Contacts OL (Overload): 1 NC + 1 NO (95-96 / 97-98)
GR (Ground): 1 NO (57-58)
SH (Short): 1 NO
Contact Rating 3 A / 250 V AC (resistive load)
Reset Mode Manual (front panel) / Electric (remote) / Automatic (adjustable) / Power-off
Fault Memory Records last 3 fault causes with corresponding current values; fault waveform recording available
Additional Functions THD (Total Harmonic Distortion) measurement, RTC clock for fault time stamping, Temperature and humidity measurement, Digital low-pass filter, Running time accumulation
Wiring Type Through-hole (贯穿型) - indicated by "H" in model code
Mounting 35 mm DIN Rail or Panel mounting
Dimensions (W x H x D) 90.3 mm × 55 mm × 126.5 mm
Net Weight 0.425 kg
Rated Insulation Voltage (Ui) 600 V AC (UL/CSA), 690 V AC (IEC 60947-4-1)
Rated Impulse Withstand Voltage (Uimp) 6 kV conforming to IEC 60947-4-1
Operating Temperature -20 °C to +60 °C
Storage Temperature -40 °C to +85 °C
IP Degree of Protection IP20 (enclosure) conforming to IEC 60529
Dielectric Strength 2 kV, 50/60 Hz, 1 minute (case to circuits) conforming to IEC 60255-5
Standards / Approvals IEC 60947-4-1, IEC 60255-6, UL, CSA, CE, CCC, RoHS
Warranty 18 months