EOCR-I3DM-WRDUHZ
The Schneider Electric EOCR-I3DM-WRDUHZ is a communication-type, integral (one-body) intelligent electronic motor protection relay from the EOCR-I3DM series . It is a high-performance device based on a 32-bit Microcontroller Unit (MCU) for real-time, high-precision monitoring and protection of three-phase AC motors using True RMS measurement
DESCRIBE
Parameter Value
Product Range EOCR (Electronic OverCurrent Relay) - I3DM Series
Product Type Communication-type, Integral (One-body) Intelligent Motor Protection Relay
Product Code / Model EOCR-I3DM-WRDUHZ (also written as EOCRI3DM-WRDUHZ)
Current Setting Range Definite Time: 0.5 ~ 80 A (direct through-hole)
Inverse Time / Thermal Inverse: 0.5 ~ 32 A (direct)
Above ranges require external CTs
Control Supply Voltage (Us) 100-240 V AC/DC (85%~110% of rated voltage) - indicated by "U"
Supply Frequency 50 / 60 Hz
Power Consumption ≤ 3 W (typical) / < 7 VA
Measurement Accuracy ±1% (True RMS, 32-bit MCU) - enhanced with "Z" revision code
THD Monitoring Total Harmonic Distortion real-time display, adjustable alarm threshold (with "Z" revision)
Protection Functions Overcurrent (OC), Undercurrent (UC), Phase Loss (Open Phase), Reverse Phase (Reversal), Locked Rotor/Stall (Sc/JA), Current Unbalance (Ub), Short Circuit (SH - optional)
Time Characteristics Definite Time / Inverse Time (1-30 classes) / Thermal Overload Inverse Time
Time Settings Overcurrent Trip Delay (O-Time): Definite time: 0.2-30 sec; Inverse time: 1-30 classes
Undercurrent Delay (U-Time): OFF, 0.5-30 sec adjustable
Start Delay (D-Time): 0-200 sec adjustable
Phase Loss Trip Time: OFF, 0.5-5 sec adjustable
Reverse Phase Trip Time: Within 0.15 sec
Locked Rotor (Running Stall) Delay: 0.2-10 sec adjustable
Current Unbalance Trip Time: 1-10 sec adjustable, setting range 10-50%
Display 5-digit 7-segment LED (3-phase current values cycle at 5-sec intervals, trip causes, setting parameters); Bar graph (load factor 65%~100%)
Communication Modbus RTU / RS-485 (2400 – 38400 bps)
Output Contacts OL (Overload): 1 NC + 1 NO (95-96 / 97-98) - D type configuration
AL (Alarm): 1 NO (07-08) for pre-alarm/undercurrent
Rating: 3 A / 250 V AC (resistive load), Ith 3A
Reset Mode Manual (front panel) / Electric (remote) / Automatic (0.5-1200 sec adjustable) / Power-off (0-1 sec) / Communication remote
Fault Memory Records last 3 fault causes with corresponding current values
Additional Functions Password protection (3-digit), Running time accumulation with alarm, Pre-alarm, Fail-safe mode selectable, Restart limit, Self-diagnosis
Wiring Type Through-hole - indicated by "H" in model code
Mounting 35 mm DIN rail mounting
Dimensions (W x H x D) Through-hole type: 70 mm × 56.3 mm × 108.1 mm
Net Weight Through-hole type: 0.355 kg
Rated Insulation Voltage (Ui) 600 V AC (UL/CSA), 690 V AC (IEC 60947-4-1)
Rated Impulse Withstand Voltage (Uimp) 6 kV conforming to IEC 60947-4-1
Operating Temperature -20 °C to +60 °C
Storage Temperature -40 °C to +85 °C
Humidity 30-85% RH (non-condensing)
IP Degree of Protection IP20 (enclosure) conforming to IEC 60529
Dielectric Strength 2 kV, 50/60 Hz, 1 minute (case to circuits) conforming to IEC 60255-5
Shock Resistance 15 gn, 11 ms conforming to IEC 60068-2-7
Vibration Resistance Panel mount: 4 gn; DIN rail: 2 gn conforming to IEC 60068-2-6
Standards / Approvals IEC 60947-4-1, IEC 60255-6, UL, CSA, CE, CCC, RoHS
Warranty 18 months
Short-circuit Protection (Fuse) BY 4 A gG
Connection Specifications Control circuit: 1×1~2.5 mm² (flexible), tightening torque 0.8~1.2 N·m
Main circuit: 1×2.5~25 mm² (flexible), tightening torque 2.5 N·m