UT150-VN/AL/RES
The Yokogawa UT150-VN/AL/RES is a robust and reliable hardwired alarm and trip module. Its key differentiator is the manual reset (latching) function, making it indispensable for critical alarm and shutdown applications where an automatic return to normal operation without operator acknowledgment is unacceptable. It provides a simple, yet highly effective, layer of safety logic.
DESCRIBE
Technical Parameters / Specifications
Category Parameter Specification
General Model UT150-VN/AL/RES
Type Single-channel Alarm Trip Module with Manual Reset
Mounting DIN rail mount inside a Yokogawa UTSX Series housing
Input Signal 4 to 20 mA DC (Load resistance: 51 Ω max.)
Burn-out Detection Up-scale (HI) or Down-scale (LO) selection via DIP switch
Output Type 2 independent SPDT Electro-mechanical Relays
Contact Rating 2 A @ 250 V AC / 30 V DC (Resistive load)
Default State Energized (Normal) / De-energized (Alarm) - configurable
Alarm Function Setpoints 2 (AL1 and AL2). Each can be set individually.
Setpoint Range Approximately 0 to 105% of span (4-20 mA)
Setting Accuracy ±0.5% of span (at 25°C)
Reset Function Manual Reset (Latching) for each alarm, via front button or remote dry contact.
Power Supply Voltage 20.4 to 31.2 V DC (Supplied to the UTSX housing)
Consumption Approx. 1.2 W (at 24 V DC)
Performance Response Time < 200 ms
Isolation 1500 V AC between Input-Output 1-Output 2-Power
Environment Operating Temperature -20°C to +60°C
Storage Temperature -40°C to +80°C
Humidity 10 to 90% RH (non-condensing)
Function and Application
Function:

Monitoring: Continuously monitors a 4-20mA process signal (e.g., pressure, level, temperature).

Comparison: Compares the signal to two pre-defined setpoint values.

Alarm Activation: Triggers its relay outputs when the process signal exceeds (or drops below) the setpoints.

Latching: The manual reset function ensures the alarm state is maintained until explicitly acknowledged by an operator, which is crucial for critical alarms that require investigation.

Interlock: Provides a hardwired safety interlock to shut down equipment if a safe operating limit is breached.