UT150-RR/RS
The Yokogawa UT150-RR/RS is a robust alarm trip module designed for 120V AC, 60 Hz powered systems and featuring a critical remote reset capability. It is the functional equivalent of the UT150-RN/RS but tailored for the North American power standard. The key difference from other UT150 models (like the VN) is its AC power supply requirement and the enhanced remote reset functionality.
DESCRIBE
Technical Parameters / Specifications
Category Parameter Specification
General Model UT150-RR/RS
Type Single-channel Alarm Trip Module with Remote Reset
Mounting DIN rail mount inside a Yokogawa UTSX Series housing
Input Signal 4 to 20 mA DC
Input Resistance Approx. 51 Ω
Burn-out Detection Up-scale (HI) or Down-scale (LO) selection via DIP switch
Output Type 2 independent SPDT Electro-mechanical Relays
Contact Rating 2 A @ 250 V AC / 30 V DC (Resistive load)
Default State Energized (Normal) / De-energized (Alarm) - configurable
Alarm Function Setpoints 2 (AL1 and AL2). Each can be set individually.
Setpoint Range Approximately 0 to 105% of span (4-20 mA)
Setting Accuracy ±0.5% of span (at 25°C)
Reset Function Local (front button) and Remote (dry contact signal)
Power Supply Voltage 120 V AC (60 Hz)
Consumption Approx. 4.5 VA (at 120 V AC)
Remote Reset Signal Dry contact input (momentary short circuit across remote reset terminals)
Contact Rating 24 V DC, 10 mA
Performance Response Time < 200 ms
Isolation 1500 V AC between Input-Output 1-Output 2-Power
Environment Operating Temperature -20°C to +60°C
Storage Temperature -40°C to +80°C
Humidity 10 to 90% RH (non-condensing)
Function and Application
Function:

Monitoring: Continuously monitors a 4-20mA process signal.

Comparison & Alarm: Triggers its relay outputs when the process signal breaches the configured setpoints.

Latching: The alarm state latches and requires a reset command to clear.

Remote Acknowledgment: The remote reset feature allows an operator in a control room to acknowledge and reset the alarm from a distant location. Application:

Used in applications identical to the UT150-RN/RS but specifically for panels and facilities where the standard available power is 120V AC, 60 Hz.

North American Markets: Primarily used in the United States, Canada, and other regions with 120V AC standard power.

Remote Process Shelters: For alarms in unmanned remote facilities where physical access for a reset is impractical.

Centralized Control: Allows all alarm acknowledgments to be performed from a central control room console.

Critical Shutdown Systems: Used in safety interlock systems where a remote reset capability is required.