DU1BG3-045N-010102-N
The Yokogawa UD1BG3-030N-6KC-2TA-N/CN is a sophisticated Dual Digital Indicating Controller from the UTAdvanced series. It is engineered to handle two independent process signals simultaneously in a single 1/8 DIN housing, making it an efficient solution for applications requiring parallel monitoring or control loops.
DESCRIBE
Technical Specifications
Category Parameter Specification
General Model UD1BG3-030N-6KC-2TA-N/CN
Series Yokogawa UTAdvanced
Type Dual Display, Dual Channel Controller
Display Two independent dual, 4-digit high-brightness red LED displays
• Primary (PV1/PV2): Process Value for each channel
• Secondary (SV1/SV2): Set Value, Alarm Value, or Output Value for each channel
Case Size 48mm x 96mm (1/8 DIN)
Input Type Dual Universal Inputs (Programmable per channel)
Supported Signals Thermocouples (TC): B, R, S, K, J, T, E, N, W, U, L, PLII
Resistance Thermometers (RTD): Pt100, JPt100
Analog Signals: DC Voltage (e.g., 0-5V, 1-5V), DC Current (e.g., 0-20mA, 4-20mA)
Accuracy ±0.2% of reading ±1 digit (for voltage/current inputs)
Control Outputs Output 1 (OUT1 for Ch1) 6KC: Relay Contact Output (Dedicated to Channel 1 control or alarm)
• Rating: 250V AC, 3A (resistive load) / 250V AC, 1A (inductive load cosφ=0.4)
Output 2 (OUT2) 2TA: Voltage Pulse Output (Assignable to Channel 1 or Channel 2 for control, used for driving Solid State Relays - SSRs)
• Output Voltage: 12 V DC ±10% (Load resistance 500Ω or higher)
• Max. Load Current: 40 mA
Alarms Number Multiple Points (Typically at least two alarms per channel, plus the one from 2TA)
Types Various modes (e.g., high limit, low limit, difference, absolute value)
Power Supply Voltage 100 to 240 V AC, 50/60 Hz
Power Consumption Approx. 9 VA max
Environmental Operating Temp. 0 to 55 °C (32 to 131 °F)
Storage Temp. -20 to 75 °C (-4 to 167 °F)
Humidity 5 to 95% RH (non-condensing)