The Yokogawa ANB10D-415/CU2N is an Intrinsic Safety Barrier, a critical component for ensuring safety in hazardous (potentially explosive) areas. It is designed for DIN rail mounting inside the safe area control panel.<br />
Its primary function is to limit the energy (voltage and current) that can be transmitted from the safe-area control system (e.g., DCS, PLC) into a hazardous area where instruments like transmitters, solenoid valves, or switches are located. This prevents the electrical signals from providing a source of ignition for flammable gases, vapors, or dusts, thus ensuring intrinsic safety (IS).
Specifications
Parameter Category Specification for ANB10D-415/CU2N
Model Number ANB10D-415/CU2N
Product Type Intrinsic Safety Barrier (Dual Channel)
Mounting Standard 35mm DIN rail mounting.
Number of Channels 2 (Dual Channel). The D in the model number often denotes a dual-channel barrier.
Approved Safety Standard FM / cULus (U.S. and Canada) for Class I, Division 2 hazardous areas. The CU2N suffix strongly indicates this certification. It may also comply with IECEx and ATEX standards.
Hazardous Area Rating The connected field device is approved for use in:**
• Class I, Division 1, Groups A, B, C, D
• Class II, Division 1, Groups E, F, G
• Class III, Division 1
[Note: The barrier itself is mounted in the safe area]
Safe Area Parameters • Supply Voltage (Ui): 250V AC/DC max (from the control system side)
• Supply Current (Ii): Typically limited by the barrier's design.
Hazardous Area Parameters • Maximum Output Voltage (Uo): ~15 V DC (estimated based on 415 code)
• Maximum Output Current (Io): ~150 mA (estimated based on 415 code)
• Maximum Output Power (Po): ~1.5 W (estimated based on 415 code)
• Maximum External Capacitance (Co): < 1.0 µF
• Maximum External Inductance (Lo): < 10 mH
These parameters define the maximum allowed capacitance and inductance for the field device and its wiring.
Field Device Compatibility Designed to protect 2-wire 4-20mA transmitters (e.g., pressure, temperature, flow) or digital input (DI) devices like mechanical switches, proximity switches, or solenoid valves.
Construction • Type: Passive Barrier. Uses a combination of current-limiting resistors and voltage-limiting Zener diodes to provide protection. Requires a dedicated, isolated earth ground for the grounding bar for proper operation.
• Terminals: Screw terminals for easy wiring.
Operating Temperature -40°C to +85°C (-40°F to +185°F)
Certifications cULus Listed (UL 913), likely also ATEX and IECEx certified. The CE mark is also present.
Key Features and Applications
Hazardous Area Protection: The core function is to prevent ignition in hazardous areas by limiting energy, enabling the safe use of electrical instruments.
Dual-Channel Design: Saves space in the control panel by providing protection for two field devices with a single module.
Passive Design: Highly reliable as it contains no active electronic components that can fail.
System Compatibility: Works seamlessly with Yokogawa control systems (like CENTUM VP) and other manufacturers' PLCs/DCS.
Global Certifications: Meets international safety standards, allowing for use in projects worldwide.
Primary Applications:
Used in Oil & Gas platforms, refineries, and pipelines.
Chemical and Pharmaceutical plants.
Paint and Coating manufacturing facilities.