The Yokogawa ALF111-S00 is a non-isolating, passive zener safety barrier designed specifically for use with thermocouples in intrinsically safe (IS) applications. Its primary function is to protect hazardous areas by limiting the amount of energy (voltage and current) that can reach the thermocouple, preventing ignition of flammable atmospheres. This model provides a direct, passive signal path for the millivolt (mV) signal from the thermocouple to the safe-area measuring device (e.g., DCS, PLC, recorder) without amplification or conversion. The "-S00" suffix denotes a specific configuration within this series.<br /> <br />
DESCRIBE
(Detailed Parameters/Specifications)
Category Parameter Specification for Model ALF111-S00
General Manufacturer Yokogawa Electric Corporation
Model ALF111-S00
Type Zener Safety Barrier (Non-isolating)
Approval ATEX, IECEx, NEPSI (Standard for intrinsic safety)
Isolation None (Passive, non-isolating)
Mounting DIN Rail Mount (35mm standard)
Input (Field Side - Hazardous Area) Device Type Thermocouple (T/C)
Intrinsic Safety (IS) Parameters Ui = 8V, Ii = 55mA, Pi = 0.1W, Ci = 5μF, Li = 10mH
(Defines the maximum energy allowed into hazardous area)
Internal Resistance Approx. 15 Ω (This is a critical parameter for signal accuracy)
Output (System Side - Safe Area) Signal Type Pass-through of thermocouple mV signal
Compatible Instruments DCS/PLC/Recorder T/C input card (must have high input impedance)
Power Supply Requirement None (Passive Device). Requires a certified IS power supply for the loop if used with a transmitter.
For direct T/C connection, no power is needed.
Performance System Accuracy Impact The barrier's internal resistance can cause a measurement error if the input impedance of the receiving device is not sufficiently high.
Operating Temperature -20 to +70°C